| Model and Specification | LYD1-RD10 | LYD1-RD20 | LYD1-RC40 | LYD1-RB60 | LYD1-RB80 |
| Rated working voltage ( Un )VAC | AC220V / AC380V | ||||
| Maxi continuous operation voltage ( Uc ) VAC | AC385V / AC420V | ||||
| Maxi discharging current (8/20 μ s ) ( Iimp ) kA | 10 | 20 | 40 | 60 | 80 |
| Nominal discharge current (8/20 μ s ) ( In ) kA | 5 | 10 | 20 | 30 | 40 |
| Voltage protective level( Up ) kV | 1.2 | 1.5 | 1.8 | 2.0 | 2.5 |
| Poles combination | 1P, 2P, 3P, 4P, 1P+NPE, 3P+NPE | ||||
| Response time ( ns ) | ≤25 | ||||
| Degree of Protection | IP20 | ||||
| Indication of invalidation | White - normal; red-invalidation; red LED shining - short circuit invalidation | ||||
| Ambient air temperature | -40°C ~ +80°C | ||||
| Installation | DIN 35mm rail | ||||