System
I
ntroduction
System capacity has
1
50
KVA,2
50
KVA,500KVA
and etc models, power module is 25KVA, users can choose freely according to the load;
System is for modular structure, consist of static switch module, monitoring module and N power module in parallel, module N + X redundancy, can proceed online expansion according to user requirements;
Monitor module, static switch module and power module can be online hot
plug; system can be set
t
ed to 1/1, 1/3, 3/1 or 3/3 come into and outgoing line way as requ
i
rements
;
Adopt master-slave parallel, multi-stage distributed control technology, no operation bottleneck, reliable performance;
All power module share battery pack
,
has perfect battery management function :battery has self-discharge function, automatic floating conversion function, temperature compensation, automatic flow fu
n
ction ;
Any power module has the balance of input, output, and charging power distribution function
;
AC input adopt continuous current mode (CCM) to operate, reduce power interference (RFI/EMI);
S
hape structure meet the requirements of the industry standard, equipment is small volume, light weight, can meet the ordinary building bearing requirements;
Optional input and output isolation transformer K values
M
aintenance manual switch, C grade lightning protection module
.
UPS can be used in parallel ,the maximum 4 pcs parallel to reach the expand demand.
Key
F
eat
ure
·
Module
s
tructure,
UPS capacity
can
be
change
d
based on loads
·N+X
r
edundancy
·
Efficiency
of UPS
is more than 9
6
%
,
environment
al protection
·
Friendly interface design of LCD
·
Microprocessor control,
self-check,
battery check by itself
·
Online static bypass,
strong protection for overload and
UPS
fault
·
R
S
232
&
SNMP
for
optional
, provide
remote control management
·I
ntelligent temperature controlled fan,
long life and low noise
·
MTBF is more than 200,000 hours
,
and MTTR is 20 minutes
|
Module Model
|
M
50
|
M75
|
|
Module Capacity
|
50
KVA
|
75
KVA
|
|
Input
/
Output Way
|
T
hree phase in three phase out
,
three phase in single phase out
,
single phase in three phase out
,
single phase in single phase out
|
|
Input PF
|
≥0.99
|
|
Input Total Harmonic Distortion
THDI(%)
|
≤3%
|
|
Module Dimension
(
W*D*H
)mm
|
4
82*700*176
|
682*700*176
|
|
Weight
(kg)
|
40
kg
|
50
kg
|
|
Model
|
3RW
200KM50
|
3RW
300KM50
|
3RW
400KM50
|
3RW
500KM50
|
3RW600K
M50
|
3RW
450KM75
|
3RW
600KM75
|
3RW
900KM75
|
|
Capacity
|
200KVA
|
300KVA
|
400KVA
|
500KVA
|
600KVA
|
450KVA
|
600KVA
|
900KVA
|
|
Type of power module
|
M50
|
M75
|
|
Input mode
|
3Ph+N+PE
|
|
Input voltage
(Vac)
|
380V/220V±20%,400V/230V±20%,415V/240V±20%
|
|
Input Frequency
(HZ)
|
50Hz±10%,60Hz±10%
|
|
Input PF
|
≥0.99
|
|
Battery voltage(Vdc)
|
±
240
|
|
Charge Time
|
10hs (2hs backup battery capacity)
|
|
Battery quantity(Pcs)
|
32-48
can be adjusted
|
|
UPS Power Factor
|
1.0
|
|
Output Voltage
(Vac)
|
380/220
V
,400/230
V
,415/240
V
|
|
Output Frequency
(HZ)
|
50Hz±4%;Mains overrun or battery mode output is 50Hz±0.2%
60Hz±4%;Mains overrun or battery mode output is 60Hz±0.2%
|
|
Output voltage Stability
|
±1%(Static);±2%(Load change from 0 ~ 100% )
|
|
Efficiency (AC mode @ full loads)
|
≥
94%
|
|
Output voltage recovery time
|
<20ms(Load change from 0 - 100% )
|
|
Overload
|
Rated Load 125% ,
r
uns 10min
s
|
|
Communication function
|
RS232
/
RS485/42
2/
dry contact
/
TCP/IP Expansion
cards
|
|
SMMP(optional)
|
Can be network monitored by SNMP adapter
|
|
Parallel function
|
Yes(for optional)
|
|
Alarm
|
Battery low-voltage, mains abnormal, overload, UPS fault, over temperature protection
|
|
Working Environment Temperature
|
-5ºC~40ºC
|
|
IP Class
|
IP3
1
|
|
Cooling
|
Speed controlled air cooling
|
|
Noise
(dB)
|
≤55dB
(Within 1 meter)
|
|
Structure
|
19 inch
es
Standard
|
|
Monitor Management System
|
UP
Supervisor
|
|
Display
|
Touchable screen
LCD/LED
|
|
Dimension(
W*D*H
)
|
600
×
1000
×
2000
|
800
×
850
×
2000/ 900
×
1000
×
2000
|
900
×
1000
×
2000
|
1400
×
850
×
2000/ 1200
×
1000
×
2200
|
1200
×
1000
×
2000
|
900
×
1000
×
2000
|
1200
×
1000
×
2000
|
1800
×
1000
×
2000
|
|
Weight
(
Kg
)
|
200
KG
|
250
KG
|
320KG
|
400
KG
|
500
KG
|
400KG
|
540KG
|
600KG
|
FAQ
1)What is your minimum order quantity?
A: For common specification, there is no minimum order quantity, and one piece could also be supplied. The difference is just the price and schedule. If your request is some special, we need to calculate it accordingly.
2)Is OEM/ODM available?
A: Yes, it is! Our products can be Customized. We have 5 senior engineers in our R&D Dept.
3)What is the Terms of Payment?
A: T/T, L/C, D/P, D/A, Western Union, Paypal and MoneyGram (for Small-amount payment).
4)Can you offer Form A or Form E or C/O?
A: Yes, it's no problem, we could apply it from our local government.
5)What's the warranty condition for your UPS?
A: 1 year warranty after the shipment of boarding date, and 1% single phase of UPS amount by free Spare Parts shipped together with each order shipment;
6)How is your delivery time?
A: It depends on your order quantity and specification, usually about 7~20days, and it won't cost more than 35days
7)What are the advantages of your company?
A: Reros has about 30 years manufacturing experience, and more than 20 years exporting experience. We promise your quality and service all the time. Adequate inventory, and supply guarantee for the subsequent renewal of supply, providing different solutions.