6ES7155-6AU01-0BN0 high quantity IM 155-6 PN ST Interface module PLC
When using PROFINET interface modules, the following basic functions are also included:
| SIMATIC ET 200SP, PROFINET interface module IM 155-6PN Standard, max. 32 I/O modules, and 16 ET 200AL modules, single hot swap, incl. server module (6ES7193-6PA00-0AA0) | |||
| General information | |||
| Product type designation | IM 155-6 PN ST | ||
| HW functional status | From FS03 | ||
Firmware version
|
Yes |
||
| Product function | |||
|
Yes; I&M0 to I&M3 | ||
|
Yes; Single hot swapping | ||
|
No | ||
| Engineering with | |||
|
V14 | ||
|
V5.5 SP4 and higher | ||
|
V2.3 / - | ||
| Configuration control | |||
| via dataset | Yes | ||
| Supply voltage | |||
| Rated value (DC) | 24 V | ||
| permissible range, lower limit (DC) | 19.2 V | ||
| permissible range, upper limit (DC) | 28.8 V | ||
| Reverse polarity protection | Yes | ||
| Short-circuit protection | Yes | ||
| Mains buffering | |||
|
10 ms | ||
| Input current | |||
| Current consumption (rated value) | 450 mA | ||
| Current consumption, max. | 550 mA | ||
| Inrush current, max. | 3.7 A | ||
| I²t | 0.09 A²·s | ||
| Power | |||
| Infeed power to the backplane bus | 4.5 W | ||
| Power loss | |||
| Power loss, typ. | 1.9 W | ||
| Address area | |||
| Address space per module | |||
|
256 byte; per input / output | ||
| Address space per station | |||
|
512 byte; Dependent on configuration | ||
| Hardware configuration | |||
| Rack | |
|
32 |
|
16 |
| Submodules | |
|
256 |
| Interfaces | |
| Number of PROFINET interfaces | 1; 2 ports (switch) |
| 1. Interface | |
| Interface types | |
|
2
Yes Yes; compatible BusAdapters: BA 2x RJ45, BA 2x FC, BA 2x M12 |
| Protocols | |
|
Yes Yes
Yes; PROFINET MRP |
| Interface types | |
| RJ 45 (Ethernet) | |
|
PROFINET with 100 Mbit/s full duplex (100BASE-TX) |
|
Yes; PROFINET with 100 Mbit/s full duplex (100BASE-TX) |
|
Yes |
|
Yes |
| Protocols | |
| PROFINET IO Device | |
| Services | |
| - IRT |
Yes; with send cycles of between 250 µs and 4 ms in increments of 125
µs |
| - PROFIenergy | Yes |
| - Prioritized startup | Yes |
| - Shared device | Yes |
| - Number of IO Controllers with shared device, max. | 2 |
| Redundancy mode | |
|
No |
| Media redundancy | |
|
Yes
No |
| Open IE communication | |
|
Yes
Yes Yes |
| Interrupts/diagnostics/status information | |
| Status indicator |
Yes
Yes Yes |
| Alarms | |
| Diagnostics function | |
| Diagnostics indication LED | |
|
Yes; green LED |
|
Yes; red LED |
|
Yes; Yellow LED |
|
Yes; green PWR LED |
|
Yes; 2x green link LEDs on BusAdapter |
| Potential separation | |
| between backplane bus and electronics |
No
Yes; 1500 V AC (type test) No |
| between PROFINET and all other circuits | |
| between supply and all other circuits | |
| Permissible potential difference | |
| between different circuits | Safety extra low voltage SELV |
| Isolation | |
| Isolation tested with | 707 V DC (type test) |
| Standards, approvals, certificates | |
| Network loading class |
2
According to Security Level 1 Test Cases V1.1.1 |
| Security level | |
| Ambient conditions | |
| Ambient temperature during operation | |
|
0 °C
60 °C 0 °C 50 °C |
| Altitude during operation relating to sea level | |
|
5 000 m |
| connection method / header | |
| ET-Connection | |
|
Yes; + 16 ET 200AL modules |
| Dimensions | |
| Width |
50 mm
117 mm 74 mm |
| Height | |
| Depth | |
| Weights | |
| Weight, approx. | 147 g; without BusAdapter |