| Output surge voltage | 0~3 5 KV, Step variable |
| Max. power energy | 20 00J |
| E nergy-storage capacitor | 4μF |
| Power | AC 220V.50Hz |
| Volume | 40 0mm× 46 0mm×3 0 0mm |
| Weight | 25 kgs |
| Operating Temperature | -10ºC-40ºC |
| Humidity | 5-90%RH |
| Elevation | <4500m |
| 1 | AC220 port: 220V,50Hz power,above 2kw |
| 2 | Power indicator: when device power on the indicator light |
| 3 |
HV closed/separated: when device power on, the HV circuit is still not work.Only adjust the knob to ZERO position and then press HV closed/separated button, the HV circuit will work.
HV closed indicator light and do HV output. When device under the HV output status,press HV closed/separated button, the HV circuit will stop work and HV separated indicator will light and meanwhile to discharge the electric charge in built-in HV capacity and tested cable. Only to adjust the knob to the ZERO position press HV closed.separated button to start HV circuit work again. |
| 4 | HV closed indicator: bright when HV circuit work |
| 5 | HV separated indicator: bright when HV circuit stop working |
| 6 | HV adjust knob: adjust the output voltage according tested cable HV withstand voltage |
| 7 |
Voltage indication: LED to display the output voltage.
When do one HV impact,if the LED display big value,it means the faulty point is breakdown,if small value,the faulty points is not breakdown. |
| 8 |
Discharging mode : three different modes of DC,Single and period.
DC is for flashover fault pre-location and common match with the HV adjustment. Single is for HV resistance fault pre-location. Press Single button to do one time discharge. Period is for pinpointing. When under this mode,the device will auto discharge according the set time period. Default is 5 seconds. |
| 9 |
Single discharge button: when device under the Single mode,press this button to do one discharge and signal output.
It is valid when other mode. |